Skip to main content
CivicBeam

592 SHERBOURNE ST

Approved

Last refreshed on Nov 15, 2026

Permit number
18 222863 ALT
Permit type
AS Alternative Solution
Applied
2018-09-10
Issued
Not available

Actions

Create monitor from this address

Exact address alerts may depend on monitor support.

Report data issueOpens your email app with this record prefilled.

Timeline

  1. Applied

    2018-09-10

  2. Issued

    Not available

  3. Completed

    2019-01-24

Project description

Alternative Solution: Where standpipe risers rise vertically through floors, or transfer horizontally from one location to another, its is proposed that protection using morgan advanced materials duct wrap be permitted to maintain the service shaft rating. As such it is proposed to protect selected horizontal portions of standpipe risers with a fire-rated wrap assembly having a 2 H fire-resistance rating (tested and rated in accordance with ULC requirements for fire resistant ducts) to Provide the required 1 H fire separation, where they are not located within a stair shaft or fire rated service space.

Permit fields

City area code
S1322
Postal code
M4X
Record created
2026-10-06T21:35:12.196421+00:00
Revision
0
Street name
SHERBOURNE
Street number
592
Street type
ST
Work
Alternative Solution
Street (from open data)
592 SHERBOURNE ST

Not a municipal ward number.

Building permits come from City public data. Confirm on the City site when it matters.