Skip to main content
CivicBeam

1001 SHEPPARD AVE E

Approved

Last refreshed on Oct 6, 2026

Permit number
21 101371 ALT
Permit type
AS Alternative Solution
Applied
2021-01-06
Issued
Not available

Actions

Create monitor from this address

Exact address alerts may depend on monitor support.

Report data issueOpens your email app with this record prefilled.

Timeline

  1. Applied

    2021-01-06

  2. Issued

    Not available

  3. Completed

    2021-03-22

Project description

The purpose of this alternative solution is to address the OBC requirement to install fire hose cabinets within floor areas that are located not more than 5 m from every required exit serving the project.On an alternative solution basis, it is proposed to omit the installation of hose cabinets within floor areas. Rather, 65 mm hose connections will be installed within the exit stair shafts as required for this project in accordance with the 2015 National Building Code of Canada (NBC) Sentence 3.2.5.10.(1) and NFPA 14-2013 "Installation of Standpipe and Hose Systems". Additionally, 65 mm hose connections will be installed where required throughout the floor area to provide the required 30 m hose coverage to the floor areas of the Project as described in the proposal.

Permit fields

City area grid code
N1729
Postal code
M2K
Record created
2026-10-06T21:39:28.596225+00:00
Revision
0
Street name
SHEPPARD
Street number
1001
Street type
AVE
street_direction
E
Work
Alternative Solution
Street (from open data)
1001 SHEPPARD AVE

Not a municipal ward number.

Building permits come from City public data. Confirm on the City site when it matters.