150 STERLING RD
ApprovedLast refreshed on Apr 4, 2026
- Permit number
- 21 109111 ALT
- Permit type
- AS Alternative Solution
- Applied
- 2021-01-26
- Issued
- Not available
Actions
Create monitor from this address
Report data issueOpens your email app with this record prefilled.Exact address alerts may depend on monitor support.
Timeline
Applied
2021-01-26
Issued
Not available
Completed
Not available
Project description
The proposed Building 3A and the underground parking garage will be provided with a standpipe system. In lieu of required fire hose stations, it is proposed to install 65 mm fire hose valve connections within the exit stairs in accordance with the NBC and NFPA 14. Fire hose valve connections will be located such that sufficient fire hose coverage of 33 m (based on 30 m hose length + 3 m hose stream) is provided in all floor areas in the building.
Permit fields
- City area grid code
- S0933
- Record created
- 2026-04-04T21:11:46.213846+00:00
- Revision
- 0
- Street name
- STERLING
- Street number
- 150
- Street type
- RD
- Work
- Alternative Solution