Skip to main content
CivicBeam

5799 YONGE ST

Approved

Last refreshed on Oct 6, 2026

Permit number
22 109137 ALT
Permit type
AS Alternative Solution
Applied
2022-01-31
Issued
Not available

Actions

Create monitor from this address

Exact address alerts may depend on monitor support.

Report data issueOpens your email app with this record prefilled.

Timeline

  1. Applied

    2022-01-31

  2. Issued

    Not available

  3. Completed

    2022-04-12

Project description

The proposed M2M Squared Phase 2 building will be provided with a standpipe system. In lieu of required fire hose stations, it is proposed to install 65 mm fire hose valve connections within the exit stairs in accordance with the NBC and NFPA 14. Fire hose valve connections will be located such that sufficient fire hose coverage of 33 m (based on 30 m hose length + 3 m hose stream) is provided in all floor areas in the building.

Permit fields

City area grid code
N1823
Postal code
M2M
Record created
2026-10-06T21:41:25.082373+00:00
Revision
0
Street name
YONGE
Street number
5799
Street type
ST
Work
Alternative Solution
Street (from open data)
5799 YONGE ST

Not a municipal ward number.

Building permits come from City public data. Confirm on the City site when it matters.