Skip to main content
CivicBeam

165 GEARY AVE

Refused

Last refreshed on Oct 6, 2026

Permit number
22 184118 ALT
Permit type
AS Alternative Solution
Applied
2022-07-30
Issued
Not available

Actions

Create monitor from this address

Exact address alerts may depend on monitor support.

Report data issueOpens your email app with this record prefilled.

Timeline

  1. Applied

    2022-07-30

  2. Issued

    Not available

  3. Completed

    2022-10-03

Project description

Alternative Solution to the change of use and renovations proposed within a unit on the Second Floor of the building; This Alternative Solution Proposal has been prepared to address the 15 min fire-resistance rating deficiency specific to providing a minimum of 1 h fire-resistance rating for the floor/ceiling assembly that separates the restaurant from the space below based on the separation between major occupancies (Group A2 and Group F2) requirements of OBC Article 3.1.3.1. and OBC Table 10.3.2.2.B. applicable to sprinklered buildings. Since upgrading the existing ceiling/floor assembly to achieve the required rating is deemed difficult, the proposed alternative compliance approach will be based on enhancing the performance of the sprinkler system through replacement of existing sprinklers protecting the space below the restaurant with new quick response sprinklers.

Permit fields

City area grid code
S0928
Postal code
M6H
Record created
2026-10-06T21:42:28.156086+00:00
Revision
0
Street name
GEARY
Street number
165
Street type
AVE
Work
Alternative Solution
Street (from open data)
165 GEARY AVE

Not a municipal ward number.

Building permits come from City public data. Confirm on the City site when it matters.